FDOT Standard Plans Index 430-020: Flared End Section

Short answer

Index 430-020 is the FDOT Standard Plan for Flared End Section, part of Series 430 (Structures). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.

Design Criteria

Design Criteria and Guidance Drainage Manual (DM) ; FDOT Design Manual (FDM) ; Drainage Design Guide (DDG); Structures Design Guidelines (SDG)

Design Assumptions and Limitations

Design Assumptions and Limitations Locate flared end sections in accordance with the Drainage Manual Chapter 3 . Additionally, when the slope intersection permits, 12" and 15" flared end sections may be located with the culvert opening as close as 8' beyond the outside edge of the shoulder. Do not use flared end sections for side drain installations.

Use reinforced concrete jackets where high velocities and/or highly erosive soils may cause disjointing. Show location(s) of reinforced concrete jackets in Plans. Use toe walls whenever the anticipated velocity of discharge and soil type are such that erosive action would occur.

Toe walls are not required where ditch pavement is provided, except when disjointing would occur if the ditch pavement should fail. Show toe wall location(s) in the Plans. When steel fiber-reinforcing is proposed as an alternative to the conventional reinforcing shown on the Index, evaluate in accordance with SDG 3.17 .

Submit for approval a Technical Special Provision identifying the fiber-reinforcing material, dosage rate and quality control provisions to the District

Materials

Materials Office. Include the Technical Special Provision in the producer's approved Quality Control Plan. For sod around end treatments, see Index 570-001 .

Payment

Payment Item number Item Description Unit Measure 430-200-BB Flared End Section (Concrete) EA 570-1-A Performance Turf SY See the BOE and Specification 430 for additional information on payment, pay item use and compensation.

What your plans must show

Plan Content Requirements for this index — the SPI's checklist for designers.

  • In the Roadway Plans: Summarize quantity by location in the Summary of Drainage or Summary of Miscellaneous Drainage Items in accordance with FDM 916 . Clearly show the location of each Flared End Section and note when reinforced concrete jackets or toe walls are to be installed.
pipeflaredconcretewallrevisionsectionsculvertoffsetlocationdescriptionjacketspecified

How PDFDepth uses this index

When a plan set cites Index 430-020, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.

Related indexes in Series 430

All FDOT Standard Plans indexes

Try it yourself — open your plan set in PDFDepth

Review, measure, and check plan sets against the standards they cite — free for 14 days.

Start for Free

Text extracted from FDOT Standard Plans FY 2026-27, a public-domain Florida state publication. Always verify against the current edition at fdot.gov. PDFDepth is not affiliated with FDOT.