FDOT Standard Plans Index 440-001: Underdrain Inspection Box
Short answer
Index 440-001 is the FDOT Standard Plan for Underdrain Inspection Box, part of Series 440 (Structures). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.
Design Criteria
Design Criteria and Guidance FDOT Design Manual (FDM) ; Drainage Manual (DM) ; Drainage Design Guide (DDG)
Design Assumptions and Limitations
Design Assumptions and Limitations The type of underdrain should be selected to meet design water removal rate and soil conditions. Caution is prescribed in the use of these typical sections since special designs may be required to satisfy project conditions. Type I underdrain is intended for minimum water removal conditions.
Type II underdrain is intended for moderate water removal conditions. Where reactive conditions may create chemical clogging, the use of an inert material and/or elimination of the geotextile may be necessary. Type III underdrain is intended for maximum water removal conditions.
Geotextile is required between the coarse aggregate or fine aggregate including those described in
General Notes
General Notes 2 and 3. Where reactive conditions may create chemical clogging, the use of an inert material and/or elimination of the geotextile may be necessary. Type V underdrain is intended for use in detention with filtration stormwater management systems and other locations which require a filtration system.
Recovery requirements should be the basis for determining length of underdrain. The designer should evaluate whether an external geotextile envelope is required around underdrain Types I and III. When required, specify the fabric in the plans.
In lieu of the inspection box detailed in Index 440-002 , Manhole Type P Alternate A, Index 425-010, with Type I Frame and Cover, Index 425-001 , may be used and is recommended when high ADT increases the chance of repeated vehicle loadings.
Payment
Payment Item number Item Description Unit Measure Index 440 - 002 Underdrain Inspection Box Index 440 - 02 Underdrain Inspection Box - AA Underdrain LF 440- 70- Underdrain Inspection Box EA 440- 73- A Underdrain Outlet Pipe LF See the BOE and Specification 440 for additional information on payment, pay item use and compensation.
What your plans must show
Plan Content Requirements for this index — the SPI's checklist for designers.
- Plan details for underdrains should include the location of: (a) Type V underdrain, (b) nonstandard locations of Type I, II, and III underdrain, (c) underdrain inspection boxes, (d) cleanouts for Type V underdrain, and (e) underdrain outlet pipes. Flow line elevations at the beginning, bends, junctions, and ends of underdrain pipes and outlet pipes should be specified.
How PDFDepth uses this index
When a plan set cites Index 440-001, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.
Related indexes in Series 440
- Index 440-002 — Underdrain Inspection Box
- Index 443-001 — Skimmers for French Drain Outlets
- Index 443-002 — Skimmers for French Drain Outlets
- Index 446-001 — Concrete Pavement Subdrainage
- Index 450-010 — Series Prestressed Florida - I Beams
- Index 450-036 — Index 450-036
- Index 450-045 — Index 450-045
- Index 450-054 — Index 450-054
Try it yourself — open your plan set in PDFDepth
Review, measure, and check plan sets against the standards they cite — free for 14 days.
Start for FreeText extracted from FDOT Standard Plans FY 2026-27, a public-domain Florida state publication. Always verify against the current edition at fdot.gov. PDFDepth is not affiliated with FDOT.