FDOT Standard Plans Index 521-509: Traffic Railing/Noise Wall (8' - 0") - Bridge

Short answer

Index 521-509 is the FDOT Standard Plan for Traffic Railing/Noise Wall (8' - 0") - Bridge, part of Series 521 (Incidental Construction). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.

Design Criteria

Design Criteria NCHRP Report 350 TL - 4; NCHRP Report 663 ; AASHTO LRFD Bridge Design Specifications ; Structures Design Guidelines ( SDG )

Design Assumptions and Limitations

Design Assumptions and Limitations The Traffic Railing / Noise Wall (8' - 0") - Bridge is the basic non - proprietary crash tested traffic railing / noise wall combination for use on FDOT bridges and approach slabs . This railing is first and foremost a traffic railing that also serves as a noise wall / barrier. To preserve the crashworthiness of the design, this railing must be used in accordance with the requirements of SDG 6.7 for all applications.

For bridge applications, design bridge decks supporting Traffic Railing / Noise Walls (8' - 0") in accordance with the requirements of SDG 4.2. For bridge decks up to a maximum thickness of 9", the two Bars 5S1 placed in the bridge deck may substitute for the longitudinal deck steel located within the limits of Bars 5V, provided that the total area of longitudinal deck steel beneath the rail ing, as required by calculation, is not reduced. The tabulated values in the SDG 4.2.5 are based on LRFD A13.3.1 yield - line theory and are intended to prevent local failure of the structural components and allow the load to be supported by the length of the wall between expansion joints for stability.

Form liners providing a textured finish are permitted on the outside face of the Traffic Railing / Noise Wall (8' - 0") with the following provisions: (1) The maximum amplitude of the form liner on the lower 3 ' - 0 " section shall be limited to ½ " depth; (2) Any form liner used above 3 ' - 0 ", must provide a thickened concrete section to maintain 2" cover. Full details of this thickened section and the form liner shall be provided in the plans. Form liners complying with the requirements of SDG 6.7 are allowed on the upper vertical portion of the inside face of the Traffic Railing / Noise Wall but are not recommended.

When the Traffic Railing / Noise Wall (8' - 0") terminates on the bridge, the End Taper shall be located at an open joint. When the Traffic Railing / Noise Wall (8' - 0") terminates on the Approach Slab, the End Taper shall terminate at Begin or End Approach S lab as shown. Indexes 400 - 509, 400 - 090 and 400 - 091 contain details for the use of Traffic Railing / Noise Walls (8' - 0") on bridge decks and approach slabs.

The details shown for installing 2" diameter conduits and associated Embedded Junction Boxes (EJBs) in traffic railings have been determined to be crashworthy in accordance with the requirements of NCHRP Report 350 , AASHTO Manual for Assessing Safety Hardware (MASH) and the AASHTO LRFD Bridge Design Specifications . To preserve the crashworthiness of Traffic Railing / Noise Walls, no more than t hree 2" diameter conduits and associated EJBs, as shown on Index 630 - Standard Plan s Instructions Topic No. 625 - 010 - 003 Index 521 - 509 Traffic Railing/Noise Wall (8' - 0") - Bridge , may be installed within the traffic railing portion (only) of the Traffic Railing / Noise Walls.

For treatment of Traffic Railing / Noise Walls (8' - 0") on skewed bridges see Index 521 - 42 7 . Slip forming of the traffic railing portion is permitted with approved shop drawings . Lap splices must meet AASHTO criteria , and concrete cover must meet FDOT requirements (2½” for slip - forming and 2” for C - I - P).

Details are available for increasing the crashworthiness of this Traffic Railing / Noise Wall to NCHRP Report 350 Test Level 5. Contact the Structures Design Office for more information.

General Notes

General Notes Sheet, specify the concrete class in accordance with the superstructure environment classification. See SDG 1.4. Show and label, by name or Index number, the Traffic Railing / Noise Wall (8' - 0") on the Plan and Elevation, Typical Section, Superstructure, Approach Slab and Finish Grade Elevations Cross Section sheets, Retaining Wall Control Drawings, and other sheets as required.

Include cross references to Standard Plan s Index 400 - 090 or 400 - 091 as appropriate. When the Traffic Railing / Noise Wall (8' - 0") ends on a bridge, provide an End Taper and terminate the low end of the End Taper at an open joint in the traffic railing, preferably at the end of a span. Continue the bridge mounted traffic railing along the remainder of the bridge.

When the Traffic Railing / Noise Wall (8' - 0") ends on an Approach Slab, provide an End Taper and terminate the low end of the End Taper at Begin or End Approach Slab. Select the low end of the taper height to accommodate the height of the continuing Traffic Railing or Concrete Barrier, or if guardrail or crash cushions are required , include a Railing End Transition as shown in the Standard. On the Superstructure section sheets, show the two Bars 5S1 placed in the bridge deck within the Bars 5V along with the rest of the reinforcing .

All concrete and Bars 5R, 5S and 5V required to construct the Traffic Railing / Noise Wall are included in the Estimated Traffic Railing Quantities. Do not include Traffic Railing / Noise Wall concrete in the estimated concrete quantities, or Bars 5R, 5S a nd 5V in the reinforcing bar lists and estimated reinforcing steel quantities for supporting bridge decks or approach slabs. Standard Plan s Instructions Topic No.

625 - 010 - 003 Index 521 - 509 Traffic Railing/Noise Wall (8' - 0") - Bridge

Payment

Payment Item number Item Description Unit Measure 521 - 5 - 2 2 Concrete Traffic Railing /Noise Wal l, Bridge , 8’ Height LF 630 - 2 - 1 6 Conduit, Furnish & Install, Embedded LF 635 - 3 - 13 Junction Box, Furnish & Install, Embedded EA

What your plans must show

Plan Content Requirements for this index — the SPI's checklist for designers.

  • In the Structures Plans: In the
railingwallnoisebridgeslabapproachjointsjointroadwaywhenopendeck

How PDFDepth uses this index

When a plan set cites Index 521-509, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.

Related indexes in Series 521

All FDOT Standard Plans indexes

Try it yourself — open your plan set in PDFDepth

Review, measure, and check plan sets against the standards they cite — free for 14 days.

Start for Free

Text extracted from FDOT Standard Plans FY 2026-27, a public-domain Florida state publication. Always verify against the current edition at fdot.gov. PDFDepth is not affiliated with FDOT.