FDOT Standard Plans Index 521-511: Concrete Barrier /Noise Wall (14' - 0")

Short answer

Index 521-511 is the FDOT Standard Plan for Concrete Barrier /Noise Wall (14' - 0"), part of Series 521 (Incidental Construction). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.

Design Criteria

Design Criteria NCHRP Report 350 TL - 4; AASHTO LRFD Bridge Design Specifications ; Structures Design Guidelines ( SDG )

Design Assumptions and Limitations

Design Assumptions and Limitations The Concrete Barrier / Noise Wall (14' - 0") is a non - proprietary concrete barrier / noise wall combination that is based on the crash tested Concrete Barrier / Noise Wall (8' - 0"). It can only be used for ground mounted applications, usually within the clear zone. This railing is first and foremost a barrier that also serves as a noise barrier.

To preserve the crashworthiness of the design, this railing must be used in accordance with the requirements of SDG 6.7 for all applications. Work this Index 521 - 511 - Concrete Barrier / Noise Wall ( 14 ' - 0") with one or more of the following: Index 521 - 51 3 - Concrete Barrier / Noise Wall T - Shaped Spread Footing, Index 521 - 51 4 - Concrete Barrier / Noise Wall L - Shaped Spread Footing or Index 521 - 51 5 - Concrete Barrier / Noise Wall Trench Footing The details as shown for installing for 2" diameter conduits and associated Embedded Junction Boxes (EJBs) in traffic railings have been determined to be crashworthy in accordance with the requirements of NCHRP Report 350 , AASHTO Manual for Assessing Safety Hardware (MASH) and the AASHTO LRFD Bridge Design Specifications . To preserve the crashworthiness of Concrete Barrier / Noise Walls, no more than two 2" diameter conduits and associated EJBs, as shown on Index 630 - 0 10, may be installed within the barrier portion (only) of the Concrete Barrier / Noise Walls.

Form liners providing a textured finish are permitted on the outside face of the Concrete Barrier / Noise Wall (14' - 0") with the following provisions: (1) The maximum amplitude of the form liner on the lower 3 ' - 0 " section shall be limited to ½ " depth; (2) Any form liner used above 3 ' - 0 ", must provide a thickened concrete section to maintain 2" cover. Full details of this thickened section and the form liner shall be provided in the plans. Form liners complying with the requirements of SDG 6.7 are allowed on the upper vertical portion of the inside face of the Concrete Barrier / Noise Wall but are not recommended.

Project specific details are required for the use of 10' - 0" and 12' - 0" tall Concrete Barrier / Noise Walls on footings. Base these details on Indexes 521 - 51 0 and 521 - 51 1.

General Notes

General Notes Sheet, specify the use of Class II or IV concrete in accordance with the environment al classification. See SDG 1.4. Standard Plan s Instructions Topic No.

625 - 010 - 003 Index 521 - 511 Concrete Barrier/Noise Wall (14' - 0") Show and label, by name or Index number, the Concrete Barrier / Noise Wall (14' - 0") on the Plan and Profile, Cross Section and other sheets as required. Include cross references to Standard Plan s Index 521 - 5 10 , 521 - 51 3, 521 - 51 4 and 521 - 51 5 as appropriate. When the approach end of the Concrete Barrier / Noise Wall (14' - 0") is within the roadway clear zone, use one of the following treatments: • Provide a Concrete Barrier / Noise Wall (8' - 0") End Taper adjacent to the Traffic Railing / Noise Wall (14' - 0") End Taper.

Continue the footing for Concrete Barrier /Noise Wall (14' - 0") as the foundation for the Concrete Barrier /Noise Wall (8' - 0") End Taper. Maintain the same slope for both tapers; approximately 1:8 (vert. : horiz.).

Select the low end of the Concrete Barrier /Noise Wall (8’ - 0” ) taper height to accommodate the height of the continuing Traffic Railing or Concrete Barrier, or if guardrail or cr ash cushions are required, include the Barrier End Transition as shown in Index 521 - 5 10 . • Flare the full height Concrete Barrier / Noise Wall (14' - 0") out beyond the clear zone. Flare rates vary based on both design speed and highway application (i.e., Interstate, urban or rural installations).

See Standard Plan s and FDM for applicable flare rates. • Terminate the full height Concrete Barrier / Noise Wall (14' - 0") within the clear zone and shield the end with a wide crash cushion. Ensure the traffic face of the wide crash cushion is offset at least 24 - inches from vertical face of Concrete Barrier / Noise Wall (14' - 0").

When the trailing end of the Concrete Barrier / Noise Wall (14' - 0") ends along the roadway within the clear zone of adjacent traffic, and the trailing end is not within the clear zone of opposing traffic, the Concrete Barrier / Noise Wall (14' - 0") can remain full height all the way to the end or the End Taper can be used. Provide Guardrail or Concrete Barrier as required to shield hazards beyond the end of the Concrete Barrier / Noise Wall. Include project specific details for 10' - 0" and 12' - 0" tall Concrete Barrier / Noise Walls.

Payment

Payment Item number Item Description Unit Measure 521 - 72 - 2 Shoulder Concrete Barrier /Noise Wall, 14' LF 521 - 72 - 2 6 Concrete Barrier /Noise Wall, 12’ (Shoulder) LF 521 - 72 - 2 5 Concrete Barrier /Noise W all , 10’ (Shoulder) LF 630 - 2 - 1 6 Conduit , Furnish & Install, Embedded LF 635 - 3 - 13 Junction Box, Furnish & Install, Embedded EA

What your plans must show

Plan Content Requirements for this index — the SPI's checklist for designers.

  • In the Roadway Plans when the Concrete Barrier / Noise Wall (14'
  • - 0") is used for ground mounted applications: In the
concretewallnoisebarrierfootingtaperspreadshapedjointopenroadwaybegin

How PDFDepth uses this index

When a plan set cites Index 521-511, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.

Related indexes in Series 521

All FDOT Standard Plans indexes

Try it yourself — open your plan set in PDFDepth

Review, measure, and check plan sets against the standards they cite — free for 14 days.

Start for Free

Text extracted from FDOT Standard Plans FY 2026-27, a public-domain Florida state publication. Always verify against the current edition at fdot.gov. PDFDepth is not affiliated with FDOT.