FDOT Standard Plans Index 521-660: Light Pole Pedestal - Bridge
Short answer
Index 521-660 is the FDOT Standard Plan for Light Pole Pedestal - Bridge, part of Series 521 (Incidental Construction). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.
Design Criteria
Design Criteria AASHTO LRFD Bridge Design Specifications ; Structures Design Guidelines ( SDG )
Design Assumptions and Limitations
Design Assumptions and Limitations Use this Index with Index 521 - 422, 521 - 423, 521 - 427, 521 - 428, 521 - 820, 515 - 0 21, 521 - 51 0 as appropriate. Anchor Bolts were designed for Design Wind, Bridge Deck Height (above MLW), Luminaire Mounting Height, and Luminaire Arm Lengths of Standard Index 715 - 0 02 Light Poles with a maximum 40 foot luminaire mounting height . Design of the additional bridge deck reinforcement is based on the minimum transverse top deck reinforcing required by the SDG .
The nominal load capacities given should be greater than the computed light pole loads calculated using the LRFD LTS Extreme Event I limit state. Axial Dead Load = 1.56 kip Wind Load Moment about Bridge Transverse Axis = 40.6 kip - ft Wind Load Moment about Bridge Longitudinal Axis = 28.3 kip - ft Dead Load Moment about Bridge Longitudinal Axis = 1.69 kip - ft Torsion about Pole Axis = 3.56 kip - ft Maximum Shear = 1.38 kip Locate pedestals near a substructure support to minimize vibration of the light poles due to traffic live loads. Locate the centerlines of pedestals a minimum 3' - 10" away from centerlines of open joints in railings and ends of railings.
Payment
Payment No separate payment is made for Light Pole Pedestals. See Payment Note on the Standard Plan .
What your plans must show
Plan Content Requirements for this index — the SPI's checklist for designers.
- In the Structures Plans: Show Light Pole Pedestals on Plan and Elevation, Superstructure and Approach Slab Supplemental Detail sheets. Use stations or longitudinal dimensions along bridge to define pedestal locations. Include anchor bolt diameters.
How PDFDepth uses this index
When a plan set cites Index 521-660, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.
Related indexes in Series 521
- Index 521-001 — Concrete Barrier
- Index 521-002 — Pier Protection Barrier
- Index 521-005 — Concrete Barrier at Toll Sites
- Index 521-010 — Opaque Visual Barrier (OVB)
- Index 521-404 — Guardrail Transitions - Existing Post & Beam Bridge Railings (Narrow & Recessed Curbs)
- Index 521-405 — Guardrail Transitions - Existing Post & Beam Bridge Railings (Wide Curbs)
- Index 521-422 — Traffic Railing (42" Vertical Shape)
- Index 521-423 — Traffic Railing (32" Vertical Shape)