FDOT Standard Plans · FY 2026-27 · Series 400: Structures

FDOT Standard Plans Index 400-011: Gravity Wall

Short answer

Index 400-011 is the FDOT Standard Plan for Gravity Wall, part of Series 400 (Structures). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.

Design Criteria

Design Criteria AASHTO LRFD Bridge Design Specifications ; Structures Design Guidelines ( SDG ) , FDOT Design Manual ( FDM )

Design Assumptions and Limitations

Design Assumptions and Limitations Index 400-011 has been developed as a self-contained standard having pre-designed wall sections; therefore, no additional reinforcing list is required in the Contract Plans. Gravity walls are generally most efficient when the difference in height between the ground levels is less than 5 feet. If the difference in height between ground levels is greater than 5 feet, other wall types or project specific designs are required.

Gravity wall design is based on the following soil criteria which covers the majority of soil types found in Florida: Classification = Cohesion less (Fine Sand) Friction Angle = 30 Degrees Moist Unit Weight of Backfill = 120 pcf Presumptive Allowable Bearing Pressure: = 2,500 psf for slopes equal to or flatter than 1:1½ = 3,300 psf for slopes steeper than 1: 1½. Corrected SPT Blow Count for foundation = 10 blows/ft. (average value within the range of depth from the base of wall to 1.5 x base width below wall).

Max. Seasonal High Water Table (SHWT) is one (1) foot below the horizontal ground surface at the toe of the wall, except as noted. In cases where the Designer considers the soil at the specific site location to be of lesser strength, an analysis is required to verify that sliding, bearing, overturning and stability requirements are satisfied.

Figures 1, 2 and 3 show the minimum toe berm widths for overall stability with the assumed soil properties listed above. The minimum toe berm width may need to be increased to satisfy other FDM criteria, such as maintenance access. Standard Plan s Instructions Topic No.

625 - 010 - 003 Index 400 - 011 Gravity Wall Figure 1 Minimum Toe Berm Width for Overall Stability - Scheme 1 Figure 2 Minimum Toe Berm Width for Overall Stability - Scheme 2 Standard Plan s Instructions Topic No. 625 - 010 - 003 Index 400 - 011 Gravity Wall Figure 3 Minimum Toe Berm Width for Overall Stability - Scheme 3 Overall stability of the wall shall be analyzed when: 1. The lower or upper slope exceeds 1:2 (vert.: horiz.); 2.

The upper slope exceeds a vertical height of 4'-0" when the lower slope is steeper than 1:6; 3. The seasonal high water (SHW) is less than 2 feet below the ground surface at the toe of the wall; or 4. The SHW is above the toe of the slope for lower slopes steeper than 1:6.

Stability of the upper slope shall be analyzed for slopes steeper than 1:2 (vert.: horiz.) with a minimum Factor of Safety = 1.3. For Scheme 1 or Scheme 2, when a roadside barrier is required above the wall (guardrail, barrier wall, etc.) the deflection space required for the barrier must be considered. Locate the barrier so that there is no conflict between guardrail posts or barrier footing and the gravity wall or soil reinforcement.

This may result in an offset greater than the minimum offset for the live load limit.

General Notes

General Notes. Reference "Index 400-011 Gravity Wall" and Wall Scheme (Scheme 1, Scheme 2 or Scheme 3) in accordance with that shown on the Standard. Where Structures component of plan set is used, place these drawings in the Structures Plans, otherwise, include these drawings in the Roadway Plans.

Elevation of wall may not be necessary for short walls or walls on constant grade.

Payment

Payment Item number Item Description Unit Measure 400-0-11 Concrete Class NS, Gravity Wall CY

Commentary

Commentary: See Standard Plans Instructions Index 521-600 Series for Concrete Barrier /Junction Slab Pay Items as required. Commentary for Reviewers: Class NS Concrete - This class of concrete was determined to be appropriate for Index 400-011 based on consultation with the Structures Design, Roadway Design, State

Materials

Materials and Construction Offices in 2005 during the LRFD redesign. This class of concrete is an economical choice and structurally appropriate for a non-flexural (gravity) earth retention system.

What your plans must show

Plan Content Requirements for this index — the SPI's checklist for designers.

  • In the Structures or Roadway Plans: Prepare Wall Control Drawings and related drawings as specified in SDM Chapter 19 and FDM 262, and include them in the plans.
  • Standard Plan s Instructions Topic No. 625
  • - 011 Gravity Wall Add any aesthetic requirements (e.g. coordinating appearance of exposed surface with adjacent walls) to the
wallheightschemejointdrainslopestrafficconcretebarssealgeneralgeotextile

How PDFDepth uses this index

When a plan set cites Index 400-011, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.