FDOT Standard Plans Index 550-012: Bridge Fencing ( Enclosed )

Short answer

Index 550-012 is the FDOT Standard Plan for Bridge Fencing ( Enclosed ), part of Series 550 (Incidental Construction). The sections below are extracted from FDOT's Standard Plans Instructions (SPI) for this index — design criteria, assumptions and limitations, and what your plans must show.

Design Criteria

Design Criteria AASHTO LRFD Bridge Design Specifications ; NCHRP Report 350 Test Level 3 Criteria (portion of fence adjacent to traffic railing only); Structures Design Guidelines ( SDG )

Design Assumptions and Limitations

Design Assumptions and Limitations The Traffic Railing mounted side of this fence is based on a design that was successfully crash tested in accordance with the AASHTO Guide Specifications for Bridge Railings Performance Level 2 pickup test. Modifications have been made to improve the crashworthiness to NCHRP Report 350 Test Level 3 Criteria. This fence can be used on Index 521 - 820 Concrete Parapets, Indexes 521 - 001 , 521 - 422, 521 - 423, 521 - 427 and 521 - 42 8 Traffic Railings, certain non - FDOT standard concrete traffic railings meeting the requirements of SDG 6.7 and on existing New Jersey and F - Shape Traffic Railings listed in the Standard Plan s Instructions Index 536 - 0 02.

Evaluate the expansion joint movements of the bridge. Expansion rails are required for concrete parapet installations at expansion joints where the total movement exceeds 1 - inch. If the total movement at an individual expansion joint is 6 - inches or less, the bridge fence will span the joint without using an expansion assembly.

If the total movement at an individual expansion joint exceeds 6 - inches, an Expansion Assembly mus t be installed at that location. Use of this fence in lieu of Index 550 - 0 10 Bridge Fencing (Vertical) , Index 550 - 0 11 Bridge Fencing (Curved Top) or Index 550 - 0 13 Bridge Fencing (Over Railroad) should be based on project and site specific requirements.

General Notes

General Notes, e.g., zinc or aluminum coated, or polyvinyl chloride (PVC) coated. If PVC coated fence is used, include the following notes in the General Notes: 1. A note specifying the color of the PVC coating for chain link fabric.

2. A note to paint the fence framework to match the color of the PVC chain link fabric. 3.

A note for preparation of galvanized steel for painting. 4. A n ote to coat tension wire and fence fittings to match the color of the PVC chain link fabric.

Consideration for Approval of Alternative Technical Proposals Alternate fencing systems may be considered for approval with concurrence from the District Structures Design Engineer. Fabricators must be listed in the Material Acceptance and Certification System (MAC) as an approved Metals Production Facility. Design calculations meeting the wind load requirements for the project site in accordance with the SDG must be submitted for review and approval by the EOR.

Technical Specifications with material and testing requirements should be submitted by the Contractor for approval prior to acceptance of any alternative technical proposal ( Contractor Savings Initiative for Design - Bid - Build projects, or Alternative Technical Concept for Design Build/P3 projects).

Payment

Payment Item number Item Description Unit Measure 550 - 10 - 343 Fencing, Type R, 7.1 - 8.0’, With Full Enclosure LF 550 - 10 - 353 Fencing, Type R, 8.1 - 10.0', With Full Enclosure LF

What your plans must show

Plan Content Requirements for this index — the SPI's checklist for designers.

  • In the Structures and/or Roadway Plans: Show and label, by name or Index number, the Bridge Fencing (Enclosed) on the Plan and Elevation, Typical Section, Superstructure and Approach Slab sheets, Retaining Wall Control Drawings, and other sheets as required. Include cross references to Standard Plan s Index 521
  • - 820 and the traffic railing standard as appropriate. Show the limits of fencing in the plans if they are not from begin of approach slab at Begin Bridge to end of approach slab at End Bridge. Show quantities for bridge fencing with quantities for Traffic Railings and/or Concrete Parapets. See FDM 902 for guidance on Estimated Quantities Report. Determine if bridge fencing requires grounding. If required, provide details in the superstructure sheets.
  • Standard Plan s Instructions Topic No. 625
  • - 012 Bridge Fencing (Enclosed) Provide locations for expansion joints requiring expansion rails or expansion assemblies in the superstructure layout sheets. Designate the required finish in the
postparapetconcreterequiredfencingrailingrailtrafficbridgeapproachslabbands

How PDFDepth uses this index

When a plan set cites Index 550-012, PDFDepth's AI Plan Review cross-references the set against the Plan Content Requirements for the FDOT indexes it cites and flags items that appear to be missing — each with a citation to the sheet. A human reviewer verifies every flag before it counts.